Power
10kVA / 9000W
Rated voltage
single-phase 240V / 230V / 220V / 208V / 200V
Input voltage range
180~ 300V (at 100% load); 100~ 300V (at 50% load)
Harmonic coefficient (total)
<5% when working at full load
Frequency
40-70 Hz
Input connection
terminal blocks
Power factor when working with full load
>0.99
Voltage
240V/230V (default) / 220V / 208V/200V, 1-phase
Voltage adjustment limits
±2% (typical), ±1% (static)
Harmonic coefficient (total)
<2% (when working with linear load)
Frequency
50Hz ±0.05Hz
Output connectors
terminal blocks
The cross factor
is 3:1
Overload capacity
126~150% - 30 seconds; 111~125% - 5 minutes; 106~110% - 10 minutes.
Voltage
240V
Charging current
Built-in charger 4A maximum
additional charger: 4A (installed inside the UPS)
Electrical connection
cable
Standard
Parallel port, RS 232, Smart slot, SNMP slot
Safety and EMS
TUV, EN62040-1, CE, Class A CISPR22
Parallel connection
1+1 redundancy
Remote control
Remote Emergency Power Off (REPO), remote on/off
Battery sharing
there is
96% economy mode (when working with full load)
Normal mode
92% (when working with full load)
Relative humidity
0% ~95% (condensation is not allowed)
Operating temperature
0 ~ 40oC
Noise level
54dB at a distance of 1m
Характеристики
Бренд
Delta
Заводские данные
Тип
MUK
Отзывы (0)
Отзывов ещё нет — ваш может стать первым.
Помогите другим пользователям с выбором - будьте первым, кто поделится своим мнением об этом товаре.
Оставить заявку
Разместите код вывода формы обратной связи в настройке контента модального окна