Floor and rack versions 19”
Appointment
office
Number of phases (input-output)
1-1
Rated power, kVA
3
Active power,
2.7 kW
Rated voltage
200 At this voltage, the rated power of the UPS is lowered to the level of 90%./208 At this voltage, the rated power of the UPS is lowered to the level of 90%./220/230/240 Perem. current
Voltage range
175-280 V perem. current (100% load)? 20-175 Vac. current (load 50-100%)
The coefficient of nonlinear current distortion
<5%
Power factor
> 0.99 (at full load)
Frequency
40~70 Hz
Voltage
200 At this voltage, the rated power of the UPS is lowered to the level of 90%./208 At this voltage, the rated power of the UPS is lowered to the level of 90%./220/230/240 Perem. current
The output power factor
is 0.9
The coefficient of nonlinear voltage distortion
< 2% (at linear load)
Voltage regulation limits
± 1% (at linear load)
Frequency
50/60 Hz ± 0.05 Hz
Overload capacity
At load < 105%: continuously 105 ~ 125%: 1 min. 125 ~ 150%: 15 sec
Cross factor
3:1
Sockets
IEC C13x6
Battery Type
72 In the post. current
The rated battery
life is 7.5 minutes (When the total load reaches 75%.)
Charging time
3 hours to 90 %
Charge current
2 A
Standard
1 SMART slot, 1 RS-232 port, 1 USB port, 1 REPO port
Normal mode (on-line)
up to 94 %
Economy mode
up to 97 %