Rated voltage
200/ 208/ 220/ 230/ 240 AC, 1P2W+PE
Voltage range
175-280 VAC (100% load), 100-175 VAC (with reduction to 50-100% load)
Frequency range
40-70 Hz
Total Harmonic Distortion Coefficient (THDi)
< 3%
Power factor
> 99% (100% load)
Connection
Input terminal
Rated voltage
200/ 208/ 220/ 230/ 240 AC, 1P2W+PE
Voltage regulation
±1%
Frequency
50/60 ± 0.05 Hz
Total harmonic distortion coefficient (THDv)
< 2% (linear load), < 4% (nonlinear load)
Power factor
1
Connection
Standard operating time model
⦁ RT-5K/6K C13 x6, C19 x2, terminal x1, programmable socket C19 x1
⦁ RT-8K/10K C13 x6, C19 x4, terminal x1, programmable socket C19 x1
A model with an extended working time
Terminal x1, programmable terminal x1
Overload ability(1)
106-125% 5 min, 126-150% 1 min, > 150% 500 ms
Current peak
The coefficient is 31
Online mode
Up to 95.5%
Eco Mode
Up to 99%
Battery Type
VRLA/ Lithium-ion
Rated voltage
The standard run-time model
⦁ RT-5K/6K 192 V DC
⦁ RT-8K/10K 240 V DC
The extended execution time model
144 V DC(2), 192-264 V DC
Charge current
The standard run-time model
⦁ RT-5K/6K 1A (default), up to 8 A
⦁ RT-8K/10K 1.5A (default), up to 8 A
Extended Execution time model
Up to 8 A
Display
Graphic LCD display with LED indicators
Port
USB, RS-232, RS-485, Mini Slot, REPO, Input Dry Contact x1, Output Dry contact x3
Dimensions (W x D x H)
The standard run-time model
⦁ RT-5K/6K 440 x 665 x 176 mm
⦁ RT-8K/10K 440 x 750 x 218 mm
A model with an extended working time
⦁ RT-5K/6K 440 x 430 x 88.2 mm
⦁ RT-8K/10K 440 x 565 x 88.2 mm
Weight
A model with a standard operating time
⦁ RT-5K/6K 54 kg
⦁ RT-8K/10K 85.5 kg
A model with an extended working time
⦁ RT-5K/6K 10.9 kg
⦁ RT-8K/10K 15.2 kg